Insulation thickness recommendation

See the recommended external-wall board thickness and the estimated heat-loss reduction for your province and wall build-up.

1. Province

Degree-day zone: 2 · approx. 2.400 degree-days

2. Wall
3. Board

Recommendation

Recommended thickness4 cmGraphite EPS (λ 0.031) · calculated minimum 3,2 cm
Current wall U-value
1,55 W/m²K
Zone target (approx.)
≤ 0,6 W/m²K
U after insulation
0,52 W/m²K
Annual heat loss (100 m²)
8.927 → 2.976 kWh
Reduction in wall heat loss
%67
How is it calculated?

Wall resistance R = Rsi + Σ(d/λ) + Rse (Rsi 0.13; Rse 0.04 m²K/W; incl. 2 cm internal and 3 cm external render). U = 1/R. For your wall R ≈ 0,65 m²K/W.

Required thickness d = λ × (1/U target − R existing), rounded up to the next standard board. Annual loss ≈ U × A × degree-days × 24 / 1000 (kWh).

Indicative only. Zone mapping and target U-values are rounded per the TS 825 approach; thermal bridges, windows and condensation are not included. A licensed engineer's calculation prevails.